Long WPL18-12SHR
Long WPL18-12SHR

Specification
Rated voltage (В)
12 V
Nominal capacity
20 hours (0.9 А to 10.50 V) 18 Ah, 10 hours (1.71 А to 10.50 V) 17.1 Ah, 5 hours (3.06 А to 10.20 V) 15.3 Ah, 1 C (18 А to 9.60 V) 11.4 Ah, 3 C (54 А to 9.60 V) 7.2 Ah
Weight
Aprox. 5.675 kg
Internal resistance (при 1 кГц)
Aprox. 10.5 mOhm
Maximum discharge current для
5 secунд: 270 А
Charging methods at 25 °С (77 °F)
Maximum charging current: 5.4 А, Use in standby mode:, Floating charging voltage from 13.5 to 13.8 V, Coefficient -3.0 мВ/˚С/Эл.
Operating temperature range
Charge from -15 °С (5 °F) to 40 °С (104 °F), Discharge from -15 °С (5 °F) to 50 °С (122 °F), Storage from -15 °С (5 °F) to 40 °С (104 °F)
Charge conservation (shelf life) at 20 °С (68 °F)
1 month 92%, 3 monthа 90%, 6 months 80%
Housing material
ABS UL94 HB, Option: Flame resistance (UL94 V-0)
Расчетный срок службы и стандарт
Ожидаемый расчетный срок службы: 6-9 years at 20 °С по данным Eurobat
Terminal
F3
*The battery must be charged before use. At higher ambient temperatures, storage time is reduced
*The content may be changed for improvement without prior notice, it is not a public offer.
Dimensions
Length
181
Width
76
Height
167
Height (full)
167

Discharge rate in watts to various final voltages at 25 °С
Vремя/Конеhное напряжение | 1.85 V | 1.80 V | 1.75 V | 1.70 V | 1.67 V | 1.65 V | 1.60 V |
5 min | 98.9 | 116 | 128 | 135 | 137 | 139 | 141 |
10 min | 67.0 | 77.1 | 84.5 | 89.1 | 90.2 | 91.7 | 92.9 |
15 min | 57.2 | 64.5 | 69.4 | 72.5 | 73.3 | 74.2 | 75.1 |
30 min | 32.7 | 35.1 | 37.7 | 39.4 | 39.8 | 40.3 | 40.8 |
60 min | 18.8 | 19.8 | 20.7 | 21.3 | 21.5 | 21.8 | 22.2 |
120 min | 11.9 | 12.4 | 12.7 | 13.1 | 13.2 | 13.3 | 13.5 |
180 min | 8.75 | 9.10 | 9.33 | 9.53 | 9.60 | 9.68 | 9.78 |
240 min | 6.63 | 6.93 | 7.12 | 7.27 | 7.32 | 7.38 | 7.46 |
300 min | 5.82 | 6.05 | 6.17 | 6.27 | 6.30 | 6.35 | 6.41 |
600 min | 3.40 | 3.52 | 3.60 | 3.67 | 3.68 | 3.72 | 3.75 |
1200 min | 1.77 | 1.83 | 1.88 | 1.92 | 1.93 | 1.95 | 1.96 |
Discharge rate in amperes to various final voltages at 25 °С
Vремя/Конеhное напряжение | 1.85 V | 1.80 V | 1.75 V | 1.70 V | 1.67 V | 1.65 V | 1.60 V |
5 min | 62.6 | 68.3 | 71.9 | 75.1 | 76.4 | 77.8 | 80.2 |
10 min | 38.6 | 41.8 | 44.3 | 46.5 | 47.4 | 48.4 | 50.1 |
15 min | 31.9 | 34.6 | 36.3 | 37.7 | 38.2 | 38.8 | 39.7 |
30 min | 17.4 | 18.7 | 19.8 | 20.7 | 21.0 | 21.4 | 21.9 |
60 min | 9.74 | 10.3 | 10.7 | 11.0 | 11.1 | 11.3 | 11.5 |
120 min | 5.98 | 6.23 | 6.39 | 6.53 | 6.58 | 6.64 | 6.72 |
180 min | 4.35 | 4.52 | 4.64 | 4.73 | 4.76 | 4.80 | 4.85 |
240 min | 3.43 | 3.52 | 3.58 | 3.62 | 3.63 | 3.65 | 3.68 |
300 min | 2.96 | 3.02 | 3.07 | 3.11 | 3.12 | 3.14 | 3.16 |
600 min | 1.73 | 1.77 | 1.80 | 1.82 | 1.83 | 1.84 | 1.85 |
1200 min | 0.893 | 0.914 | 0.931 | 0.946 | 0.952 | 0.959 | 0.962 |